    Doc: I150IGB01_04.doc 19/12/2003 p. 1 / 19

    577

    RGK60 RGK60

    PROTOCOLLO DI COMUNICAZIONE COMMUNICATION PROTOCOL

    MODBUS RTU MODBUS RTU

    ADDENDUM ADDENDUM

    I150

    IGB

    0104

  • 8/13/2019 Rgk60 Modul Lovato 3 Modbus Protokol

    2/19

  • 8/13/2019 Rgk60 Modul Lovato 3 Modbus Protokol

    3/19

    Doc: I150IGB01_04.doc 19/12/2003 p. 3 / 19

    FUNZIONI MODBUSLe funzioni disponibili sono:

    04 = Read inputregister

    Consente la lettura dellemisure disponibilinellRGK60 .

    06 = Preset singleregister

    Permette di modificare iparametri del setup

    07 = Read exceptionPermette di leggere lo statodellRGK60

    17 = Report slave IDPermette di leggereinformazioni relative

    allRGK60

    Per esempio, se si vuole leggere dall RGK60 conindirizzo 8 il valore della tensione di linea che sitrova alla locazione 2 (02 Hex), il messaggio daspedire il seguente:

    08 04 00 01 00 02 20 92

    Dove:08 = indirizzo slave.04 = funzione di lettura locazione.00 01 = indirizzo della locazione diminuito diununit, contenete il valore di tensione media di linea00 02 = numero di registri da leggere a partiredallindirizzo 01.2092 = checksum CRC.

    La risposta dell RGK60 la seguente:

    08 04 04 00 00 00 64 63 6ADove:08 = indirizzo dell RGK60 (Slave 08).04 = funzione richiesta dal Master.04 = numero di byte inviati dallRGK60 .00 00 00 64 = valore esadecimale della tensione dilinea = 100 V.63 6A = checksum CRC.

    FUNZIONE 04: READ INPUT REGISTERLa funzione 04 permette di leggere una o pi

    grandezze consecutive in memoria. Lindirizzo diciascuna grandezza e indicato nelle Tabelle 2..7riportate nelle ultime pagine del presente manuale.Come da standard Modbus, lindirizzo specificatonel messaggio va diminuito di 1 rispetto a quelloeffettivo riportato nella tabella.Se lindirizzo richiesto non compreso nella tabella oil numero di registri richiesti maggiore di 20lRGK60 ritorna un messaggio di errore ( veditabella errori).

    Richiesta Master:

    Indirizzo slave 08h

    Funzione 04h

    MSB Indirizzo registro 00h

    LSB Indirizzo registro 0Fh

    MSB Numero registri 00h

    LSB Numero registri 08h

    MSB CRC 21h

    LSB CRC 57h

    Nellesempio vengono richiesti allo slave numero 8 n.8 registri consecutivi a partire dallindirizzo 10h.Quindi vengono letti i registri dall 10h al 17h.Ilcomando termina sempre con il valore di checksumCRC.

    MODBUS FUNCTIONSThe available functions are:

    04 = Read inputregister

    Allows to read the RGK60measures.

    06 = Preset singleregister

    Allows to set the setupparameters

    07 = Read exception Allows to read the devicestatus

    17 = Report slave IDAllows to read informationabout the RGK60 .

    For instance, to read the value of the line voltage,which resides at location 2 (02 Hex) from theRGK60 with serial address 08, the message to sendis the following:

    08 04 00 01 00 02 20 92

    Whereas:08 = slave address04 = Modbus function Read input register00 01 = Address of the required register (linevoltage) decreased by one00 02 = Number of registers to be read beginningfrom address 00012092 = CRC Checksum

    The RGK60 answer is the following:

    08 04 04 00 00 00 64 63 6AWhere:08 = RGK60 address (Slave 08)04 = Function requested by the master04 = Number of bytes sent by the RGK6000 00 00 64 = Hex value of the equivalent phase-to-phase voltage (100 V)63 6A = CRC checksum

    FUNCTION 04: READ INPUT REGISTERThe Modbus function 04 allows to read one or

    more consecutive registers from the slave memory.The address of each measure is given in the tables2..7 reported in the final pages of this manual.

    As for Modbus standard, the address in the querymessage must be decreased by one from theeffective address reported in the table.If the measure address is not included in the tableor the number of requested registers exceeds 20the RGK60 will return an error code (see errortable).

    Master query:

    Slave address 08h

    Function 04h

    MSB address 00h

    LSB address 0Fh

    MSB register number 00h

    LSB register number 08h

    MSB CRC 21h

    LSB CRC 57h

    In the above example slave 08 is requested for 8consecutive registers beginning with address 10h.Thus, registers from 10h to 17h will be returned. Asusual, the message ends with the CRC checksum.

  • 8/13/2019 Rgk60 Modul Lovato 3 Modbus Protokol

    4/19

    Doc: I150IGB01_04.doc 19/12/2003 p. 4 / 19

    Risposta Slave:

    Indirizzo slave 08h

    Funzione 04h

    Numero di byte 10h

    MSB Dato 10h 00h

    LSB Dato 10h 00h

    --------------------------------------------------- ----

    MSB Dato 17h 00h

    LSB Dato 17h 00h

    MSB CRC 5Eh

    LSB CRC 83h

    La risposta composta sempre dallindirizzo delloslave, dalla funzione richiesta dal Master e dai datidei registri richiesti. La risposta termina sempre con ilvalore di checksum CRC.

    FUNZIONE 06: PRESET SINGLE REGISTERQuesta funzione permette di scrivere nei registri.Essa pu essere utilizzata solo con i registri diindirizzo superiore a 1000 Hex, e solo quando ilmotore e fermo.E possibile ad esempio impostare i parametri delsetup. I parametri di setup modificati vengono

    automaticamente salvati nella memoria ritenitiva(eeprom) e qualora il valore impostato non rientri nelvalore minimo e massimo della tabella l RGK60risponder con un messaggio di errore. Se vienerichiesto un parametro ad un indirizzo inesistenteverr risposto con un messaggio di errore. Lindirizzoed il range valido per i vari parametri pu esseretrovato nelle Tabelle 5, 6 e 7.Con la funzione 06 e inoltre possibile eseguire deicomandi utilizzando gli indirizzi ed i valori riportatinella Tabella 4.

    Richiesta Master:

    Indirizzo slave 08h

    Funzione 06h

    MSB Indirizzo registro 21h

    LSB Indirizzo registro 04h

    MSB Dato 01h

    LSB Dato 90h

    MSB CRC C3h

    LSB CRC 52h

    Nellesempio viene richiesto di modificare ilparametro P0204 allindirizzo 2105 Hex ( tensionenominale ) con il valore 400.

    Risposta Slave:La risposta un eco della domanda, cio vieneinviato al master lindirizzo del dato da modificare e ilnuovo valore del parametro.

    Slave response:

    Slave address 08h

    Function 04h

    Byte number 10h

    MSB register 10h 00h

    LSB register 10h 00h

    --------------------------------------------------- ----

    MSB register 17h 00h

    LSB register 17h 00h

    MSB CRC 5Eh

    LSB CRC 83h

    The response is always composed of the slaveaddress, the function code requested by the masterand the contents of the requested registers. Theanswer ends with the CRC.

    FUNCTION 06: PRESET SINGLE REGISTERThis function allows to write in the registers.It can be used only with registers with addresshigher than 1000 Hex, and only when the motor isstopped.For instance it is possible to change setupparameters. Modified parameters are automatically

    saved in the non-volatile eeprom memory. If thevalue is not in the correct range, the RGK60 willanswer with an error message. In the same way, ifthe parameter address is not recognised, theRGK60 will send an error response.The address and the valid range for each parameterare indicated in Tables 5, 6 and 7.With function 06, some commands can be possiblyexecuted sending the addresses and the valuesreported in Table 4.

    Master message:

    Slave address 08h

    Function 06h

    MSB register address 21h

    LSB register address 04h

    MSB data 01h

    LSB data 90h

    MSB CRC C3h

    LSB CRC 52h

    In the above message, the master wants to setparameter P0204 at address 2105 Hex (NominalVoltage) with value 400.

    Slave response:The slave response is an echo to the query, that isthe slave sends back to the master the address andthe new value of the variable.

  • 8/13/2019 Rgk60 Modul Lovato 3 Modbus Protokol

    5/19

    Doc: I150IGB01_04.doc 19/12/2003 p. 5 / 19

    FUNZIONE 07: READ EXCEPTION STATUSTale funzione permette di leggere lo stato in cui sitrova lRGK60.

    Richiesta Master:

    Indirizzo slave 08h

    Funzione 07h

    MSB CRC 47h

    LSB CRC B2h

    La tabella seguente riporta il significato del byteinviato dall RGK60 come risposta:

    BIT SIGNIFICATO

    0 Reset/OFF mode

    1 Man mode

    2 Aut mode

    3 Test mode

    4 Status Rete

    5 Status generatore

    6 Status motore

    7 Status teleruttore rete

    8 Status teleruttore generatore

    9 Status Allarme

    FUNZIONE 17: REPORT SLAVE IDQuesta funzione permette di identificare il tipo diRGK60.

    Richiesta Master.

    Indirizzo slave 08h

    Funzione 11h

    MSB CRC C6h

    LSB CRC 7Ch

    Risposta Slave:

    Indirizzo slave 08h

    Funzione 11h

    Numero byte 06h

    Dato 1 (Rev. Software) 11h

    Dato 2 (Rev. hardware) 02h

    Dato 3 (Rev. Testi) 0Ah

    Dato 4 (Rev. Parametri) 08h

    Dato 5 (Mod. Scheda Slot A) 01h

    Dato 6 (Mod. Scheda Slot B) 15h

    MSB CRC F3h

    LSB CRC 34h

    ERRORINel caso lo slave riceva un messaggio errato,segnala la condizione al master rispondendo con unmessaggio composto dalla funzione richiesta in ORcon 80 Hex, seguita da un codice di errore.Nella seguente tabella vengono riportati i codici dierrore inviati dallo slave al master

    TABELLA 1: CODICI ERRORE

    COD ERRORE

    01 Funzione non valida

    02 Indirizzo registro illegale

    03 Valore del parametro fuori range

    04 Impossibile effettuare operazione

    06Slave occupato, funzionemomentaneamente non disponibile (es.motore in marcia)

    FUNCTION 07: READ EXCEPTION STATUSThis function allows to read the status of theRGK60.

    Master query:

    Slave address 08h

    Function 07h

    MSB CRC 47h

    LSB CRC B2h

    The following table gives the meaning of the statusbyte sent by the RGK60 as answer:

    BIT MEANING

    0 Reset/OFF mode

    1 Man mode

    2 Aut mode

    3 Test mode

    4 Mains status

    5 Generator status

    6 Motor status

    7 Mains breaking status

    8 Generator breaking status

    9 Alarm status

    FUNZIONE 17: REPORT SLAVE IDThis function allows to identify the RGK60 type.

    Master query.

    Slave address 08h

    Function 11h

    MSB CRC C6h

    LSB CRC 7Ch

    Slave response:

    Slave address 08h

    Function 11h

    Byte number 06h

    Data 1Sotware revision) 11h

    Data 2 (Hardware revision) 02h

    Data 3 (Labels revision) 0Ah

    Data 4 (Parameters revision) 08h

    Dato 5 (Mod. Interface Slot A) 01h

    Dato 6 (Mod. Interface Slot B) 15h

    MSB CRC F3h

    LSB CRC 34h

    ERRORSIn case the slave receives an incorrect message, itanswers with a massage composed by the queriedfunction ORed with 80 Hex, followed by an errorcode byte.In the following table are reported the error codessent by the slave to the master:

    TABLE 1: ERROR CODES

    CODE ERROR

    01 Invalid function

    02 Invalid address

    03 Parameter out of range

    04 Function execution impossible

    06Slave busy, function momentarily notavailable (e.g. motor is running)

  • 8/13/2019 Rgk60 Modul Lovato 3 Modbus Protokol

    6/19

    Doc: I150IGB01_04.doc 19/12/2003 p. 6 / 19

    Algoritmo di calcolo del CRCCRC calculation algorithm

    CALCOLO DEL CRC (CHECKSUM)

    Esempio di calcolo:

    Frame = 0207h

    Inizializzazione CRC 1111 1111 1111 1111Carica primo byte 0000 0010Esegue xor con il primo 1111 1111 1111 1101Byte della frameEsegue primo shift a dx 0111 1111 1111 1110 1

    Carry=1,carica polinomio 1010 0000 0000 0001Esegue xor con il 1101 1111 1111 1111polinomioEsegue secondo shift dx 0110 1111 1111 1111 1Carry=1,carica polinomio 1010 0000 0000 0001Esegue xor con il 1100 1111 1111 1110polinomioEsegue terzo shift 0110 0111 1111 1111 0Esegue quarto shift 0011 0011 1111 1111 1Carry=1, carica polinomio 1010 0000 0000 0001Esegue xor con il 1001 0011 1111 1110PolinomioEseque quinto shift dx 0100 1001 1111 1111 0Eseque sesto shift dx 0010 0100 1111 1111 1Carry=1, carica polinomio 1010 0000 0000 0001Esegue xor con polinomio 1000 0100 1111 1110

    Esegue settimo shift dx 0100 0010 0111 1111 0Esegue ottavo shift dx 0010 0001 0011 1111 1Carry=1, carica polinomio 1010 0000 0000 0001

    Carica secondo byte 0000 0111della frameEsegue xor con il 1000 0001 0011 1001Secondo byte della frameEsegue primo shift dx 0100 0000 1001 1100 1Carry=1, carica polinomio 1010 0000 0000 0001Esegue xor con il 1110 0000 1001 1101polinomioEsegue secondo shift dx 0111 0000 0100 1110 1Carry=1, carica polinomio 1010 0000 0000 0001Esegue xor con il 1101 0000 0100 1111

    polinomioEsegue terzo shift dx 0110 1000 0010 0111 1Carry=1, carica polinomio 1010 0000 0000 0001Esegue xor con il 1100 1000 0010 0110polinomioEsegue quarto shift dx 0110 0100 0001 0011 0Esegue quinto shift dx 0010 0100 0000 1001 1Carry=1, carica polinomio 1010 0000 0000 0001Esegue xor con il 1001 0010 0000 1000polinomioEsegue sesto shift dx 0100 1001 0000 0100 0Esegue settimo shift dx 0010 0100 1000 0010 0Esegue ottavo shift dx 0001 0010 0100 0001 0Risultato CRC 0001 0010 0100 0001

    12h 41h

    Nota:Il byte 41h viene spedito per primo (anche see il LSB), poi viene trasmesso 12h.

    CRC CALCULATION (CHECKSUM)

    Example of CRC calculation:

    Frame = 0207h

    CRC initialization 1111 1111 1111 1111Load the first byte 0000 0010Execute xor with the first 1111 1111 1111 1101Byte of the frameExecute 1st right shift 0111 1111 1111 1110 1

    Carry=1,load polynomial 1010 0000 0000 0001Execute xor with the 1101 1111 1111 1111polynomialExecute 2ndright shift 0110 1111 1111 1111 1Carry=1,load polynomial 1010 0000 0000 0001Execute xor with the 1100 1111 1111 1110polynomialExecute 3rd right shift 0110 0111 1111 1111 0Execute 4thright shift 0011 0011 1111 1111 1Carry=1,load polynomial 1010 0000 0000 0001Execute xor with the 1001 0011 1111 1110polynomialExecute 5thright shift 0100 1001 1111 1111 0Execute 6thright shift 0010 0100 1111 1111 1Carry=1,load polynomial 1010 0000 0000 0001Execute xor with the 1000 0100 1111 1110

    polynomialExecute 7th right shift 0100 0010 0111 1111 0Execute 8th right shift 0010 0001 0011 1111 1Carry=1,load polynomial 1010 0000 0000 0001

    Load the second byte 0000 0111of the frameExecute xor with the 1000 0001 0011 1001Second byte of the frameExecute 1st right shift 0100 0000 1001 1100 1Carry=1,load polynomial 1010 0000 0000 0001Execute xor with the 1110 0000 1001 1101polynomialExecute 2ndright shift 0111 0000 0100 1110 1

    Carry=1,load polynomial 1010 0000 0000 0001Execute xor with the 1101 0000 0100 1111

    polynomialExecute 3rdright shift 0110 1000 0010 0111 1Carry=1,load polynomial 1010 0000 0000 0001Execute xor with the 1100 1000 0010 0110polynomialExecute 4thright shift 0110 0100 0001 0011 0Execute 5thright shift 0010 0100 0000 1001 1Carry=1,load polynomial 1010 0000 0000 0001Execute xor with the 1001 0010 0000 1000polynomialExecute 6thright shift 0100 1001 0000 0100 0Execute 7thright shift 0010 0100 1000 0010 0Execute 8thright shift 0001 0010 0100 0001 0CRC Result 0001 0010 0100 0001

    12h 41h

    Note:The byte 41h is sent first(even if it is theLSB), then12h is sent.

    CRC xor BYTE = CRC

    n = 0

    CRC right shift

    carry over

    CRC xor POLY = CRC

    n = n + 1

    next BYTE

    end message

    End

    n > 7

    Hex FFFF = CRC

    no

    no

    yes

    yes

  • 8/13/2019 Rgk60 Modul Lovato 3 Modbus Protokol

    7/19

    Doc: I150IGB01_04.doc 19/12/2003 p. 7 / 19

    TABELLA 2: TABLE 2:MISURE FORNITE DAL PROTOCOLLO DI COMUNICAZIONE MEASURES SUPPLIED BY SERIAL COMMUNICATION PROTOCOL

    (Utilizzabili con funzione 04) (To be used with function 04)

    INDIRIZZOADDRESS

    WORDS MISURA MEASURE UNITAUNIT FORMATOFORMAT

    02h 2 Tensione di fase rete L1 Mains phase voltage L1 V Unsigned long

    04h 2 Tensione di fase rete L2 Mains phase voltage L2 V Unsigned long

    06h 2 Tensione di fase rete L3 Mains phase voltage L3 V Unsigned long

    08h 2 Tensione di linea rete L1-L2 Mains phase to phase voltage L1-L2 V Unsigned long

    0Ah 2 Tensione di linea rete L2-L3 Mains phase to phase voltage L2-L3 V Unsigned long

    0Ch 2 Tensione di linea rete L3-L1 Mains phase to phase voltage L3-L1 V Unsigned long

    0Eh 2 Tensione di fase generatore L1 Generator phase voltage L1 V Unsigned long

    10h 2 Tensione di fase generatore L2 Generator phase voltage L2 V Unsigned long

    12h 2 Tensione di fase generatore L3 Generator phase voltage L3 V Unsigned long

    14h 2 Tensione di linea generatore L1-L2 Generator phase to phase voltage L1-L2 V Unsigned long

    16h 2 Tensione di linea generatore L2-L3 Generator phase to phase voltage L2-L3 V Unsigned long

    18h 2 Tensione di linea generatore L3-L1 Generator phase to phase voltage L3-L1 V Unsigned long

    1Ah 2 Corrente L1 Current L1 A Unsigned long

    1Ch 2 Corrente L2 Current L2 A Unsigned long

    1Eh 2 Corrente L3 Current L3 A Unsigned long

    20h 2 Potenza attiva rete L1 Mains active power L1 W Unsigned long22h 2 Potenza attiva rete L2 Mains active power L2 W Unsigned long

    24h 2 Potenza attiva rete L3 Mains active power L3 W Unsigned long

    26h 2 Potenza reattiva rete L1 Mains reactive power L1 Var Unsigned long28h 2 Potenza reattiva rete L2 Mains reactive power L2 Var Unsigned long2Ah 2 Potenza reattiva rete L3 Mains reactive power L3 Var Unsigned long2Ch 2 Potenza apparente rete L1 Mains apparent power L1 VA Unsigned long

    2Eh 2 Potenza apparente rete L2 Mains apparent power L2 VA Unsigned long

    30h 2 Potenza apparente rete L3 Mains apparent power L3 VA Unsigned long

    32h 2 Potenza attiva generatore L1 Generator active power L1 W Unsigned long

    34h 2 Potenza attiva generatore L2 Generator active power L2 W Unsigned long

    36h 2 Potenza attiva generatore L3 Generator active power L3 W Unsigned long

    38h 2 Potenza reattiva generatore L1 Generator reactive power L1 Var Unsigned long3Ah 2 Potenza reattiva generatore L2 Generator reactive power L2 Var Unsigned long3Ch 2 Potenza reattiva generatore L3 Generator reactive power L3 Var Unsigned long3Eh 2 Potenza apparente generatore L1 Generator apparent power L1 VA Unsigned long

    40h 2 Potenza apparente generatore L2 Generator apparent power L2 VA Unsigned long

    42h 2 Potenza apparente generatore L3 Generator apparent power L3 VA Unsigned long

    44h 2 Potenza attiva totale di rete Mains total active power W Unsigned long

    46h 2 Potenza reattiva totale di rete Mains total reactive power Var Unsigned long

    48h 2 Potenza apparente totale di rete Mains total apparent power VA Unsigned long

    4Ah 2 Potenza attiva totale di generatore Generator total active power W Unsigned long

    4Ch 2 Potenza reattiva totale di generatore Generator total reactive power Var Unsigned long

    4Eh 2 Potenza apparente totale di generatore Generator total apparent power VA Unsigned long

    50h 2 Fattore di potenza rete L1 Mains power factor L1 Unsigned long

    52h 2 Fattore di potenza rete L2 Mains power factor L2 Unsigned long

    54h 2 Fattore di potenza rete L3 Mains power factor L3 Unsigned long

    56h 2 Fattore di potenza totale rete Mains totla power factor Unsigned long

    58h 2 Fattore di potenza generatore L1 Generator power factor L1 Unsigned long

    5Ah 2 Fattore di potenza generatore L2 Generator power factor L2 Unsigned long

    5Ch 2 Fattore di potenza generatore L3 Generator power factor L3 Unsigned long

    5Eh 2 Fattore di potenza totale generatore Generator totla power factor Unsigned long

    60h 2 Energia attiva rete Mains total active energy Kwh*10 Unsigned long

    62h 2 Energia reattiva rete Mains total reactive power Kvarh*10 Unsigned long

    64h 2 Energia attiva generatore Generator total active energy Kwh*10 Unsigned long

  • 8/13/2019 Rgk60 Modul Lovato 3 Modbus Protokol

    8/19

    Doc: I150IGB01_04.doc 19/12/2003 p. 8 / 19

    66h 2 Energia reattiva generatore Generator total reactive energy Kvarh*10 Unsigned long

    68h 2 Frequenza di rete Mains frequency Hz*10 Unsigned long

    6Ah 2 Frequenza di generatore Generator frequency Hz*10 Unsigned long

    6Ch 2 Velocit W Speed W Rpm/min Unsigned long

    6Eh 2 Velocit calcolata della frequenza generatore Speed calculated from generator frequency Rpm/min Unsigned long

    70h 2 Velocit Pick-UP Sensor Speed Pick-UP Rpm/min Unsigned long

    72h 2 Temperatura Temperature C o F Unsigned long

    74h 2 Pressione Pression Bar o psi * 100 Unsigned long

    76h 2 Carburante Fuel % Unsigned long

    78h 2 Batteria Battery V Unsigned long

    TABELLA 3: TABLE 3:BIT DI STATO STATUS BITS

    (Utilizzabili con funzione 04) (To be used with function 04)

    INDIRIZZOADDRESS

    WORDS MISURA MEASURE UNITAUNIT FORMATOFORMAT

    160h 2 Stato bits di errore Error bits status (bit) Unsigned long

    162h 2 Stato bits di errore Error bits status (bit) Unsigned long

    170h 2 Uscite standard + espansioni Standard output + expansion (bit) Unsigned long

    180h 2Ingressi standard + espansioni (tutteprogrammabili)

    Standard input + expansion (allprogrammable)

    (bit) Unsigned long

    190h 2 Status Status (bit) Unsigned long

    Leggendo la word allindirizzo 160h vengono restituiti 32 bit con significato come da tabella:Reading the word starting at address 160h will return 32 bits with the following meaning:

    Bit Codice Allarme Code Alarm

    0 A01 Preallarme temperatura motore (sensore analogico) A01 Engine temperature warning (analog sensor)

    1 A02 Alta temperatura motore (sensore analogico) A02 High engine temperature (analog sensor)

    2 A03 Guasto sensore analogico temperatura A03 Temperature analog sensor fault

    3 A04 Alta temperatura motore (sensore digitale) A04 High engine temperature (digital sensor)

    4 A05 Preallarme pressione olio (sensore analogico) A05 Oil pressure warning (analog sensor)

    5 A06 Bassa pressione olio (sensore analogico) A06 Low oil pressure (analog sensor)

    6 A07 Guasto sensore analogico pressione A07 Pressure analog sensor fault

    7 A08 Bassa pressione olio (sensore digitale) A08 Low oil pressure (digital sensor)

    8 A09 Guasto sensore digitale pressione A09 Pressure digital sensor fault

    9 A10 Preallarme livello carburante (sensore analogico) A10 Fuel level warning (analog sensor)

    10 A11 Basso livello carburante (sensore analogico) A11 Low fuel level (analog sensor)

    11 A12 Guasto sensore analogico livello A12 Level analog sensor fault

    12 A13 Basso livello carburante (sensore digitale) A13 Low fuel level (digital sensor)

    13 A14 Tensione batteria alta A14 High battery voltage

    14 A15 Tensione batteria bassa A15 Low battery voltage

    15 A16 Batteria inefficiente A16 Inefficient battery

    16 A17 Avaria alternatore carica batteria A17 Charger alternator failure

    17 A18 Avaria segnale W A18 W signal failure

    18 A19 Bassa velocit motore W A19 Low engine W speed

    19 A20 Alta velocit motore W A20 High engine W speed

    20 A21 Mancato avviamento A21 Starting failure

    21 A22 Arresto di emergenza A22 Emergency stop

    22 A23 Arresto inaspettato A23 Unexpected stop

    23 A24 Mancato arresto A24 Engine stop failure

    24 A25 Bassa frequenza generatore A25 Low generator frequency

    25 A26 Alta frequenza generatore A26 High generator frequency26 A27 Bassa tensione generatore A27 Low generator voltage

    27 A28 Alta tensione generatore A28 High generator voltage

    28 A29 Asimmetria generatore A29 Generator asymmetry

    29 A30 Corto circuito generatore A30 Generator short-circuit

    30 A31 Sovraccarico generatore A31 Generator overload

    31 A32 Intervento protezione esterna generatore A32 External generator protection tripping

    Leggendo la word allindirizzo 162h vengono restituiti 32 bit con significato come da tabella:Reading the word starting at address 162h will return 32 bits with the following meaning:Bit Codice Allarme Code Alarm

    0 A33 Errata sequenza fasi generatore A33 Incorrect generator phase sequence

    1 A34 Errata sequenza fasi rete A34 Incorrect mains phase sequence

    2 A35 Errata impostazione frequenza di sistema A35 Wrong system frequency setting

    3 A36 Anomalia contattore generatore A36 Generator contactor failure4 A37 Anomalia contattore rete A37 Mains contactor failure

    5 A38 Richiesta manutenzione A38 Maintenance requested

    6 A39 Errore di sistema A39 System error

  • 8/13/2019 Rgk60 Modul Lovato 3 Modbus Protokol

    9/19

    Doc: I150IGB01_04.doc 19/12/2003 p. 9 / 19

    7 A40 Serbatoio travaso vuoto A40 Fuel transfer empty

    8 A41 Serbatoio travaso troppo pieno A41 Fuel transfer too full

    9 A42 Ore di noleggio esaurite A42 Rent hours exhausted

    10 A43 Basso livello liquido radiatore A43 Low radiator liquid level

    11 A44 Interruttore chiuso A44 Circuit breaker closed

    12 A45 Interruttore aperto A45 Circuit breaker open

    13 U01 Allarme utente 1 U01 Users alarm 1

    14 U02 Allarme utente 2 U02 Users alarm 2

    15 U03 Allarme utente 3 U03 Users alarm 3

    16 U04 Allarme utente 4 U04 Users alarm 4

    17 U05 Allarme utente 5 U05 Users alarm 518 U06 Allarme utente 6 U06 Users alarm 6

    19 U07 Allarme utente 7 U07 Users alarm 7

    20 U08 Allarme utente 8 U08 Users alarm 8

    21-31 Bit liberi 21-31 Free bits

    Leggendo la word allindirizzo 170h vengono restituiti 32 bit con significato come da tabella:Reading the word starting at address 170h will return 32 bits with the following meaning:

    Leggendo la word allindirizzo 180h vengono restituiti 32 bit con significato come da tabella:Reading the word starting at address 180h will return 32 bits with the following meaning:

    Leggendo la word allindirizzo 190h vengono restituiti 32 bit con significato come da tabella:Reading the word starting at address 190h will return 32 bits with the following meaning:

    Bit Significato Meaning

    0 Teleruttore rete Mains contactor

    1 Teleruttore generatore Generator contactor

    2 Uscita programmabile 1 Programmable output 1

    3 Uscita programmabile 2 Programmable output 2

    4 Uscita programmabile 3 Programmable output 3

    5 Motore Start Motor Start6 Uscita programmabile 4 Programmable output 4

    7 Uscita elettrovalvola carburante Fuel valve output

    8 Uscita programmabile 1 espansione Expansion Programmable output 1

    9 Uscita programmabile 2 espansione Expansion Programmable output 2

    10 Uscita programmabile 3 espansione Expansion Programmable output 3

    11 Uscita programmabile 4 espansione Expansion Programmable output 4

    12 Uscita programmabile 5 espansione Expansion Programmable output 5

    13 Uscita programmabile 6 espansione Expansion Programmable output 6

    14 Uscita programmabile 7 espansione Expansion Programmable output 7

    15 Uscita programmabile 8 espansione Expansion Programmable output 8

    16 Uscita programmabile 9 espansione Expansion Programmable output 9

    17 Uscita programmabile 10 espansione Expansion Programmable output 10

    18 Uscita programmabile 11 espansione Expansion Programmable output 11

    19 Uscita programmabile 12 espansione Expansion Programmable output 12

    20..31 Bit liberi Free bits

    Bit Significato Meaning

    0 Ingresso programmabile 1 Programmable input 1

    1 Ingresso programmabile 2 Programmable input 2

    2 Ingresso programmabile 3 Programmable input 3

    3 Ingresso programmabile 4 Programmable input 4

    4 Ingresso programmabile 5 Programmable input 5

    5 Ingresso programmabile 6 Programmable input 6

    6 Ingresso programmabile 7 Programmable input 7

    7 Ingresso programmabile 8 Programmable input 8

    8 Ingresso programmabile 9 Programmable input 9

    9 Ingresso programmabile 10 Programmable input 10

    10 Ingresso programmabile 11 Programmable input 11

    11 Ingresso programmabile 12 Programmable input 1212 Ingresso programmabile espansione 1 Expansion programmable input 1

    13 Ingresso programmabile espansione 2 Expansion programmable input 2

    14 Ingresso programmabile espansione 3 Expansion programmable input 3

    15 Ingresso programmabile espansione 4 Expansion programmable input 4

    16 Ingresso programmabile espansione 5 Expansion programmable input 5

    17 Ingresso programmabile espansione 6 Expansion programmable input 6

    18 Ingresso programmabile espansione 7 Expansion programmable input 7

    19 Ingresso programmabile espansione 8 Expansion programmable input 8

    20 Ingresso programmabile espansione 9 Expansion programmable input 9

    21 Ingresso programmabile espansione 10 Expansion programmable input 10

    22 Ingresso programmabile espansione 11 Expansion programmable input 11

    23 Ingresso programmabile espansione 12 Expansion programmable input 12

    24 Ingresso programmabile espansione 13 Expansion programmable input 13

    25 Ingresso programmabile espansione 14 Expansion programmable input 14

    26-31 liberi free

  • 8/13/2019 Rgk60 Modul Lovato 3 Modbus Protokol

    10/19

    Doc: I150IGB01_04.doc 19/12/2003 p. 10 / 19

    Bit Significato Meaning

    0 Allarme Alarm

    1 Motore Start Motor Start

    2 Motore Stop Motor Stop

    3 Raffreddamento Cooling

    4 Test Test

    5 Strat esterno External Strat

    6 Stop esterno External Stop

    7 Start per soglia kw Start kw trip

    8 Start EJP Start EJP

    9 Start SCR Start SCR10..31 Bit liberi Free bits

    TABELLA 4: TABLE 4:COMANDI COMMANDS(Utilizzabili con funzione 06) (To be used with function 06)

    INDIRIZZOADDRESS

    WORDS FUNZIONE FUNCTION FORMATOFORMAT

    1000h 1 Modalit OFF Operating mode OFF Unsigned integer

    1001h 1 Modalit MAN Operating mode MAN Unsigned integer

    1002h 1 Modalit AUT Operating mode AUT Unsigned integer

    1003h 1 Modalit TEST Operating mode TEST Unsigned integer

    1004h 1 Chiusura / Apertura teleruttore rete Opening / Closing mains contactor Unsigned integer

    1005h 1 Chiusura / Apertura teleruttore generatore Opening / Closing generator contactor Unsigned integer

    1006h 1 Start motore Motor start Unsigned integer

    1007h 1 Stop motore Motor stop Unsigned integer

    1100h 1 Scrittura tutta memoria eeprom Write all memory eeprom Unsigned integer

    1200h 1 Menu comandi Command menu Unsigned integer

    Per eseguire il comando e necessario usare la funzione 06 Preset single registere scrivere il valore 0001 hex allindirizzo specificato.To execute the command the user must use the function 06 Preset single register, writing value 0001Hex to the address specified..

    Per eseguire una delle funzioni disponibili nel menu comandi e necessario scrivere il valore 00xx Hex allindirizzo 1200, dove xx rappresenta il numero della vocedel menu comandi. Ad esempio per eseguire il comando C02 Reset ore manutenzionesara necessario scrivere il valore 0002 Hex allindirizzo 1200 Hexutilizzando la funzione Modbus 06. Per la lista delle funzioni disponibili nel menu comandi fare riferimento al manuale operativo.To execute one of the functions available in the Command menu it is necessary to write value 00xxHex to address 1200 Hex, where xx represents the number of

    the command menu item. For instance, to execute the command C.02 Maintenance hour reset , the user must write value 0002 hex to the address 1200 hex usingModbus function 06. See the operating manual for the complete list of the command menu functions.

    IMPOSTAZIONE PARAMETRITramite il protocollo Modbus e possibile accedere ai parametri dei menubase, esteso e funzioni. Nelle seguenti tabelle e riportato il range diimpostazione in formato numerico. Per interpretare correttamente lacorrispondenza fra valore numerico e funzione selezionata e/o unita dimisura, fare riferimento al manuale operativo dellRGK60 .I seguenti parametri sono sempre disponibili in lettura, mentrepossono essere modificati solo quando lo strumento in modalitOFF.

    PARAMETER SETTINGUsing the Modbus protocol it is possible to access the base, advanced andfunction menu parameters. In the following tables it is reported the numericalrange for each parameter. To correctly understand the correspondencebetween the numeric value and the selected function and/or the unit ofmeasure, please see the RGK60 operating manual.The following parameters can be read at any time, while the write-access is possible only when the RGK60 is OFF mode.

    PARAMETRI MENU UTILITA UTILITY PARAMETERS MENU(Utilizzabili con funzioni 04 e 06) (To be used with functions 04 and 06)

    INDIRIZZOADDRESS

    WORDS PARAMETRO PARAMETER RANGE FORMATOFORMAT

    2002h 1 P0101 Lingue English/Italiano/Francais/Pourtugues/Espanol

    P0101 Languages Unsigned integer

    2003h 1 P0102 Anno 1989-2089 P0102 Year Unsigned integer

    2004h 1 P0103 Mese 1-12 P0103 Month Unsigned integer

    2005h 1 P0104 Giorno Mese 1-31 P0104 Day of the month Unsigned integer

    2006h 1 P0105 Giorno Settimana 1-7 P0105 Day of the week Unsigned integer

    2007h 1 P0106 Ora 0-23 P0106 Hour Unsigned integer

    2008h 1 P0107 Minuti 0-59 P0107 Minutes Unsigned integer

    2009h 1 P0108 Secondi 0-59 P0108 Seconds Unsigned integer

    200Ah 1 P0109 Set orologio allalimentazione OFF/ON P0109 Clock setting at power-up Unsigned integer

    200Bh 1 P0110 Ritorno pagina principale (sec) OFF/5-999 P0110 Default page return (sec) Unsigned integer

    200Ch 1 P0111 Contrasto display (%) 0-100 P0111 Display contrast (%) Unsigned integer

    200Dh 1 P0112 Retroilluminazione dispaly (%) 0-100 P0112 Display Backlight (%) Unsigned integer

    200Eh 1P0113 Ritardo spegnimento (min)retroilluminazione

    OFF/1-900 P0113 Delay backlight off (min) Unsigned integer

  • 8/13/2019 Rgk60 Modul Lovato 3 Modbus Protokol

    11/19

    Doc: I150IGB01_04.doc 19/12/2003 p. 11 / 19

    PARAMETRI MENU GENERALI GENERAL PARAMETERS MENU(Utilizzabili con funzioni 04 e 06) (To be used with functions 04 and 06)

    INDIRIZZOADDRESS

    WORDS PARAMETRO RANGE PARAMETER FORMATOFORMAT

    2102h 1 P0201 Rapporto TA 1.0-2000.0 P0201 CT ratio Unsigned integer

    2103h 1 P0202 Rapporto TV 1.0-500.0 P0202 VT ratio Unsigned integer

    2104h 1 P0203 Tipo di collegamento 3N-3-2N-1N P0203 Wiring configuration Unsigned integer

    2105h 1 P0204 Tensione nominale (V) 100-50000 P0204 Rated voltage (V) Unsigned integer

    2106h 1 P0205 Frequenza (Hz) 50/60 P0205 Frequency (Hz) Unsigned integer

    2107h 1 P0206 Rapporto RPM / W 0.001-50.000 P0206 RPM / W ratio Unsigned integer

    2108h 1 P0207 Giri nominale Motore (RPM) 750-3600 P0207 Rated engine speed (RPM) Unsigned integer

    2109h 1 P0208 Scelta unit di misura C/bar-F/psi P0208 Unit of measure Unsigned integer

    210Ah 1 P0209 Interbloccco rete/generatore (sec) 0.0-60.0 P0209 MAINS/GEN interlock (sec) Unsigned integer

    210Bh 1P0210 Ritardo ON/OFF rete/generatore(sec)

    1-60 P0210 M/G feedback delay (sec) Unsigned integer

    210Ch 1 P0211 Modo OFF/RESET allalimentazione OFF/ON P0211 RESET mode at power-up Unsigned integer

    210Dh 1 P0212 Tempo sirena (sec) OFF/1-60 P0212 Siren time (sec) Unsigned integer

    210Eh 1 P0213 Sirena prima di avviamento (sec) OFF/1-60 P0213 Siren before starting (sec) Unsigned integer

    210Fh 1 P0214 Sirena PC in linea (sec OFF/1-60 P0214 Siren PC on line (sec) Unsigned integer

    2110h 1 P0215 Capacit serbatoio OFF/1-30000 P0215 Fuel capacity Unsigned integer

    PARAMETRI MENU BATTERIA BATTERIA PARAMETERS MENU(Utilizzabili con funzioni 04 e 06) (To be used with functions 04 and 06)

    INDIRIZZOADDRESS

    WORDS PARAMETRO RANGE PARAMETER FORMATOFORMAT

    2202h 1 P0301 Tensione batteria (V) 1.0-2000.0 P0301 Battery voltage (V) Unsigned integer

    2203h 1 P0302 Limite tensione MAX (%) 1.0-500.0 P0302 MAX voltage limit (%) Unsigned integer2204h 1 P0303 Limite tensione MIN (%) 3N-3-2N-1N P0303 MIN voltage limit (%) Unsigned integer

    2205h 1 P0304 Ritardo tensione MIN/MAX (sec) 100-50000 P0304 MIN/MAX voltage delay (sec) Unsigned integer

    PARAMETRI MENU AVVIAMENTO MOTORE ENGINE START PARAMETERS MENU(Utilizzabili con funzioni 04 e 06) (To be used with functions 04 and 06)

    INDIRIZZOADDRESS

    WORDS PARAMETRO RANGE PARAMETER FORMATOFORMAT

    2302h 1P0401 Tensione alternatore motore avviato(V)

    OFF/3-30 P0401 Alternator voltage engine started (V) Unsigned integer

    2303h 1P0402 Tensione generatore motore avviato(%)

    OFF/10-100% P0402 Generator voltage engine started (%) Unsigned integer

    2304h 1P0403 Frequenza generatore motoreavviato (%)

    OFF/10-100% P0403 Generator frequency engine started(%)

    Unsigned integer

    2305h 1 P0404 Segnale W motore avviato (RPM) OFF/10-100% P0404 W signal engine started (RPM) Unsigned integer

    2306h 1 P0405 Preriscaldo candelette (sec) OFF/1-60 P0405 Glow-plugs preheating (sec) Unsigned integer

    2307h 1 P0406 Numero tentativi avviamento 1-10 P0406 Starting attempts number Unsigned integer

    2308h 1 P0407 Durata tentativo avv. (sec) 1-30 P0407 Attempts starting time (sec) Unsigned integer

    2309h 1 P0408 Pausa tentativi avviamento (sec) 1-30 P0408 Pause between starting (sec) Unsigned integer

    230Ah 1P0409 Pausa avviamento interrotto esuccessivo (sec)

    OFF/1-20 P0409 Aborted starting & subsequent (sec) Unsigned integer

    230Bh 1 P0410 Tempo decelerazione (sec) OFF/1-180 P0410 Deceleration time (sec) Unsigned integer

    230Ch 1 P0411 Tempo raffreddamento (sec) 1-3600 P0411 Cooling time (sec) Unsigned integer

    230Dh 1 P0412 Tempo magnete arresto (sec) OFF/1-60 P0412 Stop magnet time (sec) Unsigned integer

    230Eh 1 P0413 Ritardo valvola gas (sec) OFF/1-10 P0413 Gas valve delay (sec) Unsigned integer

    230Fh 1 P0414 Tempo cicchetto (sec) OFF/1-10 P0414 Priming time (sec) Unsigned integer

    2310h 1 P0415 Tempo valvola aria (sec) OFF/1-10 P0415 Choke valve time (sec) Unsigned integer

    2311h 1 P0416 Limite stacco aria (%) 0-100 P0416 Choke OFF limit (%) Unsigned integer

    PARAMETRI MENU CONTROLLO MOTORE ENGINE CONTROL PARAMETERS MENU(Utilizzabili con funzioni 04 e 06) (To be used with functions 04 and 06)

    INDIRIZZOADDRESS

    WORDS PARAMETRO RANGE PARAMETER FORMATOFORMAT

    2402h 1 P0501 Scelta sensore pressione (1) P0501 Pressure sensor selection Unsigned integer

    2403h 1 P0502 Scelta sensore temperatura (1) P0502 Temperature sensor selection Unsigned integer

    2404h 1 P0503 Scelta sensore carburante (1) P0503 Fuel sensor selection Unsigned integer

    2405h 1 P0504 Preallarme pressione MIN 0.1-180.0 P0504 MIN pressure warning Unsigned integer

    2406h 1 P0505 Limite pressione MIN 0.1-180.0 P0505 MIN pressure limit Unsigned integer

    2407h 1 P0506 Preallarme temperatura MAX 40-285 P0506 MAX temperature warning Unsigned integer

    2408h 1 P0507 Limite temperatura MAX 40-285 P0507 MAX temperature limit Unsigned integer

    2409h 1 P0508 Preallarme carburante MIN (%) 0-100 P0508 MIN fuel warning (%) Unsigned integer

    240Ah 1 P0509 Livello carburante MIN (%) 0-100 P0509 MIN fuel level (%) Unsigned integer

    240Bh 1P0510 Inibizione allarmi allavviamento(sec)

    1-30 P0510 Alarms inhibition at starting (sec) Unsigned integer

    240Ch 1 P0511 Limite velocit W MAX (%) 100-120 P0511 MAX W speed limit (%) Unsigned integer

    240Dh 1 P0512 Ritardo velocit W MAX (sec) 3-20 P0512 MAX W speed delay (sec) Unsigned integer

    240Eh 1 P0513 Limite velocit W MIN (%) 80-100 P0513 MIN W speed limit (%) Unsigned integer240Fh 1 P0514 Ritardo velocit W MIN (sec) 0-600 P0514 MIN W speed delay (sec) Unsigned integer

    2410h 1 P0515 Ritardo A03 (min) OFF/1-60 P0515 Delay A03 (min) Unsigned integer

    (1) Prima di impostare il tipo di sensore, verificare la curva di risposta mediante il software di set-up.(1) Before setting the type of sensor, it i s advisable to check the curve characteristic by means of the set-up software

  • 8/13/2019 Rgk60 Modul Lovato 3 Modbus Protokol

    12/19

    Doc: I150IGB01_04.doc 19/12/2003 p. 12 / 19

    PARAMETRI MENU CONTROLLO RETE MAINS CONTROL PARAMETERS MENU(Utilizzabili con funzioni 04 e 06) (To be used with functions 04 and 06)

    INDIRIZZOADDRESS

    WORDS PARAMETRO RANGE PARAMETER FORMATOFORMAT

    2502h 1 P0601 Limite tensione MIN (%) 70-100 P0601 MIN voltage limit (%) Unsigned integer

    2503h 1 P0602 Ritardo tensione MIN (sec) 0-600 P0602 MIN voltage delay (sec) Unsigned integer

    2504h 1 P0603 Limite tensione MAX (%) 100-120 P0603 MAX voltage limit (%) Unsigned integer

    2505h 1 P0604 Ritardo tensione MAX (sec) 0-600 P0604 MAX voltage delay (sec) Unsigned integer

    2506h 1 P0605 Ritardo rete nei limiti (sec) 1-600 P0605 MAINS into limits delay(sec) Unsigned integer

    2507h 1 P0606 Isteresi limiti MIN/MAX (%) 0.0-5.0 P0606 MIN/MAX hysteresis limits (%) Unsigned integer

    2508h 1 P0607 Limite asimmetria MAX (%) 5-20 P0607 MAX asymmetry limit (%) Unsigned integer

    2509h 1 P0608 Ritardo asimmetria MAX (sec) 0-600 P0608 MAX asymmetry delay (sec) Unsigned integer

    250Ah 1 P0609 Limite frequenza MAX (%) 100-120/OFF P0609 MAX frequency limit (%) Unsigned integer

    250Bh 1 P0610 Limite frequenza MIN (%) OFF/80-100 P0610 MIN frequency limit (%) Unsigned integer

    250Ch 1 P0611 Ritardo frequenza MIN/MAX (sec) 0-600 P0611 MIN/MAX frequency delay (sec) Unsigned integer

    250Dh 1P0612 Controllo RETE OFF/interno/esterno OFF/INT/EXT P0612 MAINS control

    OFF/internal/external)Unsigned integer

    250Eh 1P0613 Controllo RETE in modoRESET/OFF

    OFF/ON/OFF+GLOB/ON+GLOB

    P0613 MAINS control in RESET/OFF mode Unsigned integer

    250Fh 1P0614 Controllo RETE in modo MAN OFF/ON/OFF+G

    LOB/ON+GLOBP0614 MAINS control in MAN mode Unsigned integer

    PARAMETRI MENU CONTROLLO GENERATORE ENGINE CONTROL PARAMETERS MENU(Utilizzabili con funzioni 04 e 06) (To be used with functions 04 and 06)

    INDIRIZZOADDRESS

    WORDS PARAMETRO RANGE PARAMETER FORMATOFORMAT

    2602h 1 P0701 Limite tensione MIN (%) 70-100 P0701 MIN voltage limit (%) Unsigned integer2603h 1 P0702 Ritardo tensione MIN (sec) 0-600 P0702 MIN voltage delay (sec) Unsigned integer

    2604h 1 P0703 Limite tensione MAX (%) 100-120 P0703 MAX voltage limit (%) Unsigned integer

    2605h 1 P0704 Ritardo tensione MAX (sec) 0-600 P0704 MAX voltage delay (sec) Unsigned integer

    2606h 1 P0705 Ritardo generatore nei limiti (sec) 0-600 P0705 Generator into limits delay (sec) Unsigned integer

    2607h 1 P0706 Isteresi limiti MIN/MAX(%) 0.0-5.0 P0706 MIN/MAX hysteresis limits (%) Unsigned integer

    2608h 1 P0707 Limite asimmetria MAX(%) 5-20 P0707 MAX asymmetry limit (%) Unsigned integer

    2609h 1 P0708 Ritardo asimmetria MAX (sec) 0-600 P0708 MAX asymmetry delay (sec) Unsigned integer

    260Ah 1 P0709 Limite frequenza MAX (%) 100-120/OFF P0709 MAX frequency limit (%) Unsigned integer

    260Bh 1 P0710 Ritardo frequenza MAX (sec) 0-200 P0710 MAX frequency delay (sec) Unsigned integer

    260Ch 1 P0711 Limite frequenza MIN (%) OFF/80-100 P0711 MIN frequency limit (%) Unsigned integer

    260Dh 1 P0712 Ritardo frequenza MIN (sec) 0-600 P0712 MIN frequency delay (sec) Unsigned integer

    260Eh 1 P0713 Controllo gen. OFF/interno/esterno OFF/INT/EXT P0713 Gen. Control (OFF/internal/external) Unsigned integer

    260Fh 1 P0714 Ritardo allarmi A27 A28 (sec) 5-240 P0714 A27 A28 alarms delay (sec) Unsigned integer

    PARAMETRI MENU PROTEZIONE GENERATORE ENGINE PROTECTION PARAMETERS MENU(Utilizzabili con funzioni 04 e 06) (To be used with functions 04 and 06)

    INDIRIZZOADDRESS

    WORDS PARAMETRO RANGE PARAMETER FORMATOFORMAT

    2702h 1 P0801 Corrente nominale generatore (A) OFF/5-10000 P0801 Rated generator current (A) Unsigned integer

    2703h 1 P0802 Limite corrente max. (%) 100-500/OFF P0802 MAX current limit (%) Unsigned integer

    2704h 1 P0803 Ritardo corrente max (sec) 0.0-60.0 P0803 MAX current delay (sec) Unsigned integer

    2705h 1 P0804 Scelta curva di protezione (1) P0804 Thermal protection curve selection Unsigned integer

    (1) Prima di impostare la classe di protezione, verificare la caratteristica dintervento mediante il software di set-up.Attenzione!! Il TA esterno deve essere scelto in funzione della corrente massima definita nel parametr1 P0802 e P0804.1) Before setting the protection class, it is advisable to check the trip characteristic by means of the set-up software.Caution!! The external CT must be chosen on the basis of the maximum current defined by the parameters P0802 and P0804.

    PARAMETRI MENU TEST E MANUTENZIONE TEST E MAINTENANCE PARAMETERS MENU(Utilizzabili con funzioni 04 e 06) (To be used with functions 04 and 06)

    INDIRIZZOADDRESS

    WORDS PARAMETRO RANGE PARAMETER FORMATOFORMAT

    2802h 1 P0901 Giorno inizio TEST 1-7 P0901 TEST beginning day Unsigned integer

    2803h 1 P0902 Ora inizio TEST (h) 00-23 P0902 TEST beginning hour (h) Unsigned integer

    2804h 1 P0903 Minuti inizio test (min) 00-59 P0903 TEST beginning Minutes (min) Unsigned integer

    2805h 1 P0904 Intervallo tra i TEST (giorni) 1-30 P0904 Interval between TESTS (days) Unsigned integer

    2806h 1 P0905 Durata TEST (min) OFF/1-60 P0905 TEST duration (min) Unsigned integer

    2807h 1 P0906 Test con carico OFF/ON P0906 Test with load Unsigned integer

    2808h 1 P0907 Intervallo di manutenzione (h) OFF/1-999 P0907 Maintenance interval (h) Unsigned integer

    2809h 1 P0908 Test automatico con stop esterno OFF/ON P0908 Automatic test with external stop Unsigned integer

  • 8/13/2019 Rgk60 Modul Lovato 3 Modbus Protokol

    13/19

    Doc: I150IGB01_04.doc 19/12/2003 p. 13 / 19

    PARAMETRI MENU PORTA DI COMUNICAZIONE COMUNICATION PORT PARAMETERS MENU(Utilizzabili con funzioni 04 e 06) (To be used with functions 04 and 06)

    INDIRIZZOADDRESS

    WORDS PARAMETRO RANGE PARAMETER FORMATOFORMAT

    2902h 1 P1001 Indirizzo porta seriale 1-99 P1001 Serial port address Unsigned integer

    2903h 1P1002 Baud-Rate RS232 OFF/1200-

    38400P1002 RS-232 baud rate Unsigned integer

    2904h 1P1003 Baud-Rate RS485 OFF/1200-

    38400P1003 RS-485 baud rate Unsigned integer

    2905h 1 P1004 Canale modem RS232/RS485 P1004 Modem channel Unsigned integer

    2906h 1P1005 Parit 0=no 1=pari

    2=dispariP1005 Parity Unsigned integer

    2907h 1P1006 Protocollo Rs2332 0=Lovato

    1=Modbus RTUP1006 Protocol Rs232 Unsigned integer

    2908h 1P1007 Protocollo Rs2485 0=Lovato

    1=Modbus RTUP1007 Protocol Rs485 Unsigned integer

    PARAMETRI MENU VARIE MISCELLANEOUS PARAMETERS MENU(Utilizzabili con funzioni 04 e 06) (To be used with functions 04 and 06)

    INDIRIZZOADDRESS

    WORDS PARAMETRO RANGE PARAMETER FORMATOFORMAT

    2A02h 1 P1101 Start su limite max OFF/ON P1101 Max engine power starting Unsigned integer

    2A03h 1 P1102 Limite max avviamento (kW) 0-9999 P1102 Engine start threshold (kW) Unsigned integer

    2A04h 1 P1103 Ritardo limite max avviamento (sec) 0-999 P1103 Engine start threshold delay (sec) Unsigned integer

    2A05h 1 P1104 Limite minimo arresto (kW) 0-9999 P1104 Engine stop threshold (kW) Unsigned integer2A06h 1 P1105 Ritardo limite minimo arresto (sec) 0-999 P1105 Engine stop threshold delay (sec) Unsigned integer

    2A07h 1 P1106 Carico fittizio OFF/ON P1106 Dummy load Unsigned integer

    2A08h 1 P1107 Carico ON (kW) 0-9999 P1107 Dummy load ON (kW) Unsigned integer

    2A09h 1 P1108 Ritardo carico ON (sec) 0-999 P1108 Dummy load ON delay (sec Unsigned integer

    2A0Ah 1 P1109 Carico OFF (kW) 0-9999 P1109 Dummy load OFF (kW) Unsigned integer

    2A0Bh 1 P1110 Ritardo carico OFF (sec) 0-999 P1110 Dummy load OFF delay (sec) Unsigned integer

    2A0Ch 1 P1111 Ore di noleggio (h) 0-60000 P1111 Rent hours (h) Unsigned integer

    2A0Dh 1P1112 Scelta modo Normal/EJP/

    EJP-T/SCRP1112 Mode select Unsigned integer

    2A0Eh 1 P1113 Ritardo start motore (EJP) 0-99 P1113 Start motor delay (EJP) Unsigned integer

    2A0Fh 1 P1114 Ritardo commutazione 0-30 P1114 Changeover delay Unsigned integer

    2A10h 1 P1115 Blocco ricommutazione OFF/ON P1115 Changeover block Unsigned integer

    2A11h 1P1116 Tempo di ciclo on dummy load (min) OFF/1-600 P1116 Dummy load cycle duration ON

    (min)Unsigned integer

    2A12h 1

    P1117 Tempo di ciclo off dummy load (min) OFF/1-600 P1117 Dummy load cycle duration OFF

    (min)

    Unsigned integer

  • 8/13/2019 Rgk60 Modul Lovato 3 Modbus Protokol

    14/19

    Doc: I150IGB01_04.doc 19/12/2003 p. 14 / 19

    PARAMETRI MENU INPUT PROGRAMMABILI INPUT PROGRAMMABLE PARAMETERS MENU(Utilizzabili con funzioni 04 e 06) (To be used with functions 04 and 06)

    (1)Vedi lelenco delle funzioni disponibili nella tabella Ingressi programmabili.(1) See the list of the available functions in the Programmable inputs table.

    PARAMETRI MENU USCITE PROGRAMMABILI OUTPUT PROGRAMMABLE PARAMETERS MENU(Utilizzabili con funzioni 04 e 06) (To be used with functions 04 and 06)

    INDIRIZZOADDRESS

    WORDS PARAMETRO RANGE PARAMETER FORMATOFORMAT

    2C02h 1P1301 Uscita morsetto 5.3-5.4-5.5

    (Funzione..)

    1 P1301 Output terminal 5.3-5.4-5.5(Function..)

    Unsigned integer

    2C03h 1P1302 Uscita morsetto 6.2

    (Funzione..)

    1 P1302 Output terminal 6.2(Function..)

    Unsigned integer

    2C04h 1P1303 Uscita morsetto 6.3

    (Funzione..)

    1 P1303 Output terminal 6.3(Function..)

    Unsigned integer

    2C05h 1P1304 Uscita morsetto 6.5

    (Funzione..)

    1 P1304 Output terminal 6.5Function..)

    Unsigned integer

    (1) Vedi lelenco delle funzioni disponibili nella tabella Uscite programmabili(1) See the list of the available functions in the Programmable outputs table.

    INDIRIZZOADDRESS

    WORDS PARAMETRO RANGE PARAMETER FORMATOFORMAT

    2B02h 1 P1201 Ingresso morsetto 8.1 (1) P1201 Input terminal 8.1 Unsigned integer

    2B03h 1 8.1 Tipo contatto NO/NC 8.1 Contact type Unsigned integer

    2B04h 1 8.1 Ritardo chiusura (sec) 0.0-6000.0 8.1 Opening delay (sec) Unsigned integer

    2B05h 1 8.1 Ritardo apertura (sec) 0.0-6000.0 8.1 Closing delay (sec) Unsigned integer

    2B06h 1 P1202 Ingresso morsetto 8.2 (1) P1202 Input terminal 8.2 Unsigned integer

    2B07h 1 8.2 Tipo contatto NO/NC 8.2 Contact type Unsigned integer2B08h 1 8.2 Ritardo chiusura (sec) 0.0-6000.0 8.2 Opening delay (sec) Unsigned integer

    2B09h 1 8.2 Ritardo apertura (sec) 0.0-6000.0 8.2 Closing delay (sec) Unsigned integer

    2B0Ah 1 P1203 Ingresso morsetto 8.3 (1) P1203 Input terminal 8.3 Unsigned integer

    2B0Bh 1 8.3 Tipo contatto NO/NC 8.3 Contact type Unsigned integer

    2B0Ch 1 8.3 Ritardo chiusura (sec) 0.0-6000.0 8.3 Opening delay (sec) Unsigned integer

    2B0Dh 1 8.3 Ritardo apertura (sec) 0.0-6000.0 8.3 Closing delay (sec) Unsigned integer

    2B0Eh 1 P1204 Ingresso morsetto 8.4 (1) P1204 Input terminal 8.4 Unsigned integer

    2B0Fh 1 8.4 Tipo contatto NO/NC 8.4 Contact type Unsigned integer

    2B10h 1 8.4 Ritardo chiusura (sec) 0.0-6000.0 8.4 Closing delay (sec) Unsigned integer

    2B11h 1 8.4 Ritardo apertura (sec) 0.0-6000.0 8.4 Opening delay (sec) Unsigned integer

    2B12h 1 P1205 Ingresso morsetto 8.5 (1) P1205 Input terminal 8.5 Unsigned integer

    2B13h 1 8.5 Tipo contatto NO/NC 8.5 Contact type Unsigned integer

    2B14h 1 8.5 Ritardo chiusura (sec) 0.0-6000.0 8.5 Closing delay (sec) Unsigned integer

    2B15h 1 8.5 Ritardo apertura (sec) 0.0-6000.0 8.5 Opening delay (sec) Unsigned integer

    2B16h 1 P1206 Ingresso morsetto 8.6 (1) P1206 Input terminal 8.6 Unsigned integer2B17h 1 8.6 Tipo contatto NO/NC 8.6 Contact type Unsigned integer

    2B18h 1 8.6 Ritardo chiusura (sec) 0.0-6000.0 8.6 Closing delay (sec) Unsigned integer

    2B19h 1 8.6 Ritardo apertura (sec) 0.0-6000.0 8.6 Opening delay (sec) Unsigned integer

    2B1Ah 1 P1207 Ingresso morsetto 8.7 (1) P1207 Input terminal 8.7 Unsigned integer

    2B1Bh 1 8.7 Tipo contatto NO/NC 8.7 Contact type Unsigned integer

    2B1Ch 1 8.7 Ritardo chiusura (sec) 0.0-6000.0 8.7 Closing delay (sec) Unsigned integer

    2B1Dh 1 8.7 Ritardo apertura (sec) 0.0-6000.0 8.7 Opening delay (sec) Unsigned integer

    2B1Eh 1 P1208 Ingresso morsetto 8.8 (1) P1208 Input terminal 8.8 Unsigned integer

    2B1Fh 1 8.8 Tipo contatto NO/NC 8.8 Contact type Unsigned integer

    2B20h 1 8.8 Ritardo chiusura (sec) 0.0-6000.0 8.8 Closing delay (sec) Unsigned integer

    2B21h 1 8.8 Ritardo apertura (sec) 0.0-6000.0 8.8 Opening delay (sec) Unsigned integer

    2B22h 1 P1209 Ingresso morsetto 8.9 (1) P1209 Input terminal 8.9 Unsigned integer

    2B23h 1 8.9 Tipo contatto NO/NC 8.9 Contact type Unsigned integer

    2B24h 1 8.9 Ritardo chiusura (sec) 0.0-6000.0 8.9 Closing delay (sec) Unsigned integer

    2B25h 1 8.9 Ritardo apertura (sec) 0.0-6000.0 8.9 Opening delay (sec) Unsigned integer

    2B26h 1 P1210 Ingresso morsetto 9.1 (1) P1210 Input terminal 9.1 Unsigned integer

    2B27h 1 9.1 Tipo contatto NO/NC 9.1 Contact type Unsigned integer

    2B28h 1 9.1 Ritardo chiusura (sec) 0.0-6000.0 9.1 Closing delay (sec) Unsigned integer

    2B29h 1 9.1 Ritardo apertura (sec) 0.0-6000.0 9.1 Opening delay (sec) Unsigned integer

    2B30h 1 P1211 Ingresso morsetto 9.2 (1) P1211 Input terminal 9.2 Unsigned integer

    2B31h 1 9.2 Tipo contatto NO/NC 9.2 Contact type Unsigned integer

    2B32h 1 9.2 Ritardo chiusura (sec) 0.0-6000.0 9.2 Closing delay (sec) Unsigned integer

    2B33h 1 9.2 Ritardo apertura (sec) 0.0-6000.0 9.2 opening delay (sec) Unsigned integer

    2B34h 1 P1212 Ingresso morsetto 9.3 (1) P1212 Input terminal 9.3 Unsigned integer

    2B35h 1 9.3 Tipo contatto NO/NC 9.3 Contact type Unsigned integer

    2B36h 1 9.3 Ritardo chiusura (sec) 0.0-6000.0 9.3 Closing delay (sec) Unsigned integer

    2B37h 1 9.3 Ritardo apertura (sec) 0.0-6000.0 9.3 Opening delay (sec) Unsigned integer

  • 8/13/2019 Rgk60 Modul Lovato 3 Modbus Protokol

    15/19

    Doc: I150IGB01_04.doc 19/12/2003 p. 15 / 19

    PARAMETRI MENU INPUT OPTIONAL OPTIONAL INPUT PARAMETERS MENU(Utilizzabili con funzioni 04 e 06) (To be used with functions 04 and 06)

    (1)Vedi lelenco delle funzioni disponibili nella tabella Ingressi programmabili.(1) See the list of the available functions in the Programmable inputs table.

    INDIRIZZOADDRESS

    WORDS PARAMETRO RANGE PARAMETER FORMATOFORMAT

    2D02h 1 P1401 Ingresso morsetto I.01 (1) P1401 Input terminal I.01 Unsigned integer

    2D03h 1 Tipo contatto NO/NC Contact type Unsigned integer

    2D04h 1 Ritardo chiusura (sec) 0.0-6000.0 Opening delay (sec) Unsigned integer

    2D05h 1 Ritardo apertura (sec) 0.0-6000.0 Closing delay (sec) Unsigned integer

    2D06h 1 P1402 Ingresso morsetto I.02 (1) P1402 Input terminal I.02 Unsigned integer

    2D07h 1 Tipo contatto NO/NC Contact type Unsigned integer2D08h 1 Ritardo chiusura (sec) 0.0-6000.0 Opening delay (sec) Unsigned integer

    2D09h 1 Ritardo apertura (sec) 0.0-6000.0 Closing delay (sec) Unsigned integer

    2D0Ah 1 P1403 Ingresso morsetto I.03 (1) P1403 Input terminal I.03 Unsigned integer

    2D0Bh 1 Tipo contatto NO/NC Contact type Unsigned integer

    2D0Ch 1 Ritardo chiusura (sec) 0.0-6000.0 Opening delay (sec) Unsigned integer

    2D0Dh 1 Ritardo apertura (sec) 0.0-6000.0 Closing delay (sec) Unsigned integer

    2D0Eh 1 P1404 Ingresso morsetto I.04 (1) P1404 Input terminal I.04 Unsigned integer

    2D0Fh 1 Tipo contatto NO/NC Contact type Unsigned integer

    2D10h 1 Ritardo chiusura (sec) 0.0-6000.0 Closing delay (sec) Unsigned integer

    2D11h 1 Ritardo apertura (sec) 0.0-6000.0 Opening delay (sec) Unsigned integer

    2D12h 1 P1405 Ingresso morsetto I.05 (1) P1405 Input terminal I.05 Unsigned integer

    2D13h 1 Tipo contatto NO/NC Contact type Unsigned integer

    2D14h 1 Ritardo chiusura (sec) 0.0-6000.0 Closing delay (sec) Unsigned integer

    2D15h 1 Ritardo apertura (sec) 0.0-6000.0 Opening delay (sec) Unsigned integer

    2D16h 1 P1406 Ingresso morsetto I.06 (1) P1406 Input terminal I.06 Unsigned integer2D17h 1 8.6 Tipo contatto NO/NC Contact type Unsigned integer

    2D18h 1 8.6 Ritardo chiusura (sec) 0.0-6000.0 Closing delay (sec) Unsigned integer

    2D19h 1 8.6 Ritardo apertura (sec) 0.0-6000.0 Opening delay (sec) Unsigned integer

    2D1Ah 1 P1407 Ingresso morsetto I.07 (1) P1407 Input terminal I.07 Unsigned integer

    2D1Bh 1 Tipo contatto NO/NC Contact type Unsigned integer

    2D1Ch 1 Ritardo chiusura (sec) 0.0-6000.0 Closing delay (sec) Unsigned integer

    2D1Dh 1 Ritardo apertura (sec) 0.0-6000.0 Opening delay (sec) Unsigned integer

    2D1Eh 1 P1408 Ingresso morsetto I.08 (1) P1408 Input terminal I.08 Unsigned integer

    2D1Fh 1 Tipo contatto NO/NC Contact type Unsigned integer

    2D20h 1 Ritardo chiusura (sec) 0.0-6000.0 Closing delay (sec) Unsigned integer

    2D21h 1 Ritardo apertura (sec) 0.0-6000.0 Opening delay (sec) Unsigned integer

    2D22h 1 P1409 Ingresso morsetto I.09 (1) P1409 Input terminal I.09 Unsigned integer

    2D23h 1 Tipo contatto NO/NC Contact type Unsigned integer

    2D24h 1 Ritardo chiusura (sec) 0.0-6000.0 Closing delay (sec) Unsigned integer

    2D25h 1 Ritardo apertura (sec) 0.0-6000.0 Opening delay (sec) Unsigned integer

    2D26h 1 P1410 Ingresso morsetto I.10 (1) P1410 Input terminal I.10 Unsigned integer

    2D27h 1 Tipo contatto NO/NC Contact type Unsigned integer

    2D28h 1 Ritardo chiusura (sec) 0.0-6000.0 Closing delay (sec) Unsigned integer

    2D29h 1 Ritardo apertura (sec) 0.0-6000.0 Opening delay (sec) Unsigned integer

    2D2Ah 1 P1411 Ingresso morsetto I.11 (1) P1411 Input terminal I.11 Unsigned integer

    2D2Bh 1 Tipo contatto NO/NC Contact type Unsigned integer

    2D2Ch 1 Ritardo chiusura (sec) 0.0-6000.0 Closing delay (sec) Unsigned integer

    2D2Dh 1 Ritardo apertura (sec) 0.0-6000.0 opening delay (sec) Unsigned integer

    2D2Eh 1 P1412 Ingresso morsetto I.12 (1) P1412 Input terminal I.12 Unsigned integer

    2D2Fh 1 Tipo contatto NO/NC Contact type Unsigned integer

    2D30h 1 Ritardo chiusura (sec) 0.0-6000.0 Closing delay (sec) Unsigned integer

    2D31h 1 Ritardo apertura (sec) 0.0-6000.0 Opening delay (sec) Unsigned integer

    2D32h 1 P1413 Ingresso morsetto I.13 (1) P1413 Input terminal I.13 Unsigned integer

    2D33h 1 Tipo contatto NO/NC Contact type Unsigned integer

    2D34h 1 Ritardo chiusura (sec) 0.0-6000.0 Closing delay (sec) Unsigned integer

    2D35h 1 Ritardo apertura (sec) 0.0-6000.0 opening delay (sec) Unsigned integer2D36h 1 P1414 Ingresso morsetto I.14 (1) P1414 Input terminal I.14 Unsigned integer

    2D37h 1 Tipo contatto NO/NC Contact type Unsigned integer

    2D38h 1 Ritardo chiusura (sec) 0.0-6000.0 Closing delay (sec) Unsigned integer

    2D39h 1 Ritardo apertura (sec) 0.0-6000.0 Opening delay (sec) Unsigned integer

  • 8/13/2019 Rgk60 Modul Lovato 3 Modbus Protokol

    16/19

    Doc: I150IGB01_04.doc 19/12/2003 p. 16 / 19

    PARAMETRI MENU USCITE OPTIONAL OPTIONAL OUTPUT PARAMETERS MENU(Utilizzabili con funzioni 04 e 06) (To be used with functions 04 and 06)

    INDIRIZZOADDRESS

    WORDS PARAMETRO RANGE PARAMETER FORMATOFORMAT

    2E02h 1P1501 Uscita morsetto O.01

    (Funzione..)

    1 P1501 Output terminal O.01(Function..)

    Unsigned integer

    2E03h 1P1502 Uscita morsetto O.02

    (Funzione..)

    1 P1502 Output terminal O.02(Function..)

    Unsigned integer

    2E04h 1P1503 Uscita morsetto O.03

    (Funzione..)

    1 P1503 Output terminal O.03(Function..)

    Unsigned integer

    2E05h 1P1504 Uscita morsetto O.04

    (Funzione..)

    1 P1504 Output terminal O.04(Function..)

    Unsigned integer

    2E06h 1P1505 Uscita morsetto O.05

    (Funzione..)

    1 P1505 Output terminal O.05(Function..)

    Unsigned integer

    2E07h 1P1506 Uscita morsetto O.06

    (Funzione..)

    1 P1506 Output terminal O.06(Function..)

    Unsigned integer

    2E08h 1P1507 Uscita morsetto O.07

    (Funzione..)

    1 P1507 Output terminal O.07(Function..)

    Unsigned integer

    2E09h 1P1508 Uscita morsetto O.08

    (Funzione..)

    1 P1508 Output terminal O.08(Function..)

    Unsigned integer

    2E0Ah 1P1509 Uscita morsetto O.09

    (Funzione..)

    1 P1509 Output terminal O.09(Function..)

    Unsigned integer

    2E0Bh 1P1510 Uscita morsetto O.10

    (Funzione..)

    1 P1510 Output terminal O.10(Function..)

    Unsigned integer

    2E0Ch 1P1511 Uscita morsetto O.11

    (Funzione..)

    1 P1511 Output terminal O.11(Function..)

    Unsigned integer

    2E0Dh 1P1512 Uscita morsetto O.12

    (Funzione..)

    1 P1512 Output terminal O.12(Function..)

    Unsigned integer

    (1) Vedi lEelenco delle funzioni disponibili nella tabella Uscite programmabili(1) See the list of the available functions in the Programmable outputs table.

    Ingressi programmabili (Funzione) Programmable inputs (Function)

    0 Disabilitato Disable

    1 Pressione olio Oil pressure

    2 Temperatura acqua motore Water engine temperature

    3 Livello carburante Fuel level

    4 Arresto di emergenza Emergency stop

    5 Stop a distanza Remote stop

    6 Avviamento a distanza Remote starting

    7 Avviamento a distanza senza stop Remote starting without cooling

    8 Avvia test automatico Start automatic test9 Protezione termica generatore Generator thermal protection

    10 Supervisione OFF Supervision Off

    11 Blocco setup Set-up block

    12 Controllo RETE esterno External MAINS control

    13 Controllo GEN esterno External GEN control

    14 Telecommutazione Automatic changeover

    15 Feed-back contattore RETE MAINS contactor feed-back

    16 Feed-back contattore GEN GEN contactor feed-back

    17 Serbatoio vuoto Fuel tank empty

    18 Start rabbocco Filling start

    19 Stop rabbocco Filling stop

    20 Serbatoio troppo pieno Fuel tank too full

    21 Blocco tastiera (1) Keyboard lock (1)

    22 Liquido radiatore Radiator liquid

    23 Sirena off Siren off24 Allarme stato interruttore Circuit breaker status alarm

    25 Allarme utente 1 Users alarm 1

    26 Allarme utente 2 Users alarm 2

    27 Allarme utente 3 Users alarm 3

    28 Allarme utente 4 Users alarm 4

    29 Allarme utente 5 Users alarm 5

    30 Allarme utente 6 Users alarm 6

    31 Allarme utente 7 Users alarm 7

    32 Allarme utente 8 Users alarm 8

    (1)Con la funzione Blocco tastiera abilitata i tasti Off/Reset Man Aut Test Start Stop Mains Gen Enter non sono operativi.(1) When the Keyboard lock is enabled, OFF/RESET - MAN AUT TEST- START STOP MAINS GEN ENTER keys are inoperative.

  • 8/13/2019 Rgk60 Modul Lovato 3 Modbus Protokol

    17/19

    Doc: I150IGB01_04.doc 19/12/2003 p. 17 / 19

    Uscite programmabili (Funzione) Programmable outputs (Function)

    TABELLA 9: TABLE 9:LISTA EVENTI EVENT LOG(Utilizzabili con funzione 04) (Da rev. firmware 18 alla 21) (To be used with function 04) (From firmware rev. 18 to 21)

    INDIRIZZOADDRESS

    WORDS PARAMETRO PARAMETER RANGE FORMATOFORMAT

    6002h 1 Codice evento nr. 32 (piu recente) Code of event nr. 32 (most recent) 0..62 Unsigned integer

    6003h 1 Secondi evento nr. 32 Event nr. 32 - Seconds 0..59 Unsigned integer

    6004h 1 Minuti evento nr. 32 Event nr. 32 - Minutes 0..59 Unsigned integer

    6005h 1 Ore evento nr. 32 Event nr. 32 - Hours 0..23 Unsigned integer

    6006h 1 Giorno evento nr.32 Event nr. 32 - Day 0..31 Unsigned integer

    6007h 1 Mese evento nr. 32 Event nr. 32 - Month 1..12 Unsigned integer

    6008h 1 Anno evento nr. 32 Event nr. 32 - Year 0..99 Unsigned integer

    6009h 1 Codice evento nr. 31 Code of event nr. 31 0..62 Unsigned integer

    600Ah 1 Secondi evento nr. 31 Event nr. 31 - Seconds 0..59 Unsigned integer

    600Bh 1 Minuti evento nr. 31 Event nr. 31 - Minutes 0..59 Unsigned integer

    600Ch 1 Ore evento nr. 31 Event nr. 31 - Hours 0..23 Unsigned integer

    600Dh 1 Giorno evento nr. 31 Event nr. 31 - Day 0..31 Unsigned integer

    600Eh 1 Mese evento nr. 31 Event nr. 31 - Month 1..12 Unsigned integer

    600Fh 1 Anno evento nr. 31 Event nr. 31 - Year 0..99 Unsigned integer

    60DBh 1 Codice evento nr. 01 (piu vecchio) Code of event nr. 01 (oldest) 0..62 Unsigned integer

    60DCh 1 Secondi evento nr. 01 Event nr. 01 - Seconds 0..59 Unsigned integer

    60DDh 1 Minuti evento nr. 01 Event nr. 01 - Minutes 0..59 Unsigned integer

    60DEh 1 Ore evento nr. 01 Event nr. 01 - Hours 0..23 Unsigned integer

    60DFh 1 Giorno evento nr. 01 Event nr. 01 - Day 0..31 Unsigned integer

    60E0h 1 Mese evento nr. 01 Event nr. 01- Month 1..12 Unsigned integer

    60E1h 1 Anno evento nr. 01 Event nr. 01 - Year 0..99 Unsigned integer

    Il significato del codice dellevento puo essere determinato nella seguente tabella. In caso non siano registrati eventi viene ritornato il codice 0.The meaning of the event code can be found in the following table. In case there is no recorded event code 0 will be returned

    0 Disabilitata Disable

    1 Allarme globale Global alarm

    2 Elettrovalvola carburante Fuel solenoid valve

    3 Sirena Siren

    4 Deceleratore Decelerator

    5 Magnete stop Stop magnet

    6 Candelette Glow-plugs

    7 Valvola gas Gas valve

    8 Valvola aria Air valve

    9 Valvola cicchetto Priming valve\0 Pompa rabbocco Topping-up pump

    11 Carico fittizio Dummy load

    12 Aria compressa Compressed air

    13 Modo funzionamento Operating mode

    14 Rete non presente Mains not present

    15 Motore in moto Engine running

    16 Motore in allarme Engine failure

    17 Basso carburante Low fuel level

    18 Carico fittizio L1 Dummy load L1

    19 Carico fittizio L2 Dummy load L2

    20 Carico fittizio L3 Dummy load L3

    21 Allarme globale 1 Global alarm 2

    22 Allarme globale 2 Global alarm 3

    23-76 Allarmi A1-A45 e UA1-UA8 A1-A45 and UA1-UA8 alarms

  • 8/13/2019 Rgk60 Modul Lovato 3 Modbus Protokol

    18/19

    Doc: I150IGB01_04.doc 19/12/2003 p. 18 / 19

    TABELLA 9: TABLE 9:LISTA EVENTI EVENT LOG(Utilizzabili con funzione 04) (Da rev. firmware 22) (To be used with function 04) (From firmware rev. 22)

    INDIRIZZOADDRESS

    WORDS PARAMETRO PARAMETER RANGE FORMATOFORMAT

    6002h 1 Codice evento nr. 255 (piu recente) Code of event nr. 255 (most recent) 0..62 Unsigned integer

    6003h 1 Secondi evento nr. 255 Event nr. 255 - Seconds 0..59 Unsigned integer

    6004h 1 Minuti evento nr. 255 Event nr. 255 - Minutes 0..59 Unsigned integer

    6005h 1 Ore evento nr. 255 Event nr. 255 - Hours 0..23 Unsigned integer

    6006h 1 Giorno evento nr.255 Event nr. 255 - Day 0..31 Unsigned integer6007h 1 Mese evento nr. 255 Event nr. 255 - Month 1..12 Unsigned integer

    6008h 1 Anno evento nr. 255 Event nr. 255 - Year 0..99 Unsigned integer

    6009h 1 Codice evento nr. 254 Code of event nr. 254 0..62 Unsigned integer

    600Ah 1 Secondi evento nr. 254 Event nr. 254 - Seconds 0..59 Unsigned integer

    600Bh 1 Minuti evento nr. 254 Event nr. 254 - Minutes 0..59 Unsigned integer

    600Ch 1 Ore evento nr. 254 Event nr. 254 - Hours 0..23 Unsigned integer

    600Dh 1 Giorno evento nr. 254 Event nr. 254 - Day 0..31 Unsigned integer

    600Eh 1 Mese evento nr. 254 Event nr. 254 - Month 1..12 Unsigned integer

    600Fh 1 Anno evento nr. 254 Event nr. 254 - Year 0..99 Unsigned integer

    66F4h 1 Codice evento nr. 01 (piu vecchio) Code of event nr. 01 (oldest) 0..62 Unsigned integer

    66F5h 1 Secondi evento nr. 01 Event nr. 01 - Seconds 0..59 Unsigned integer

    66F6h 1 Minuti evento nr. 01 Event nr. 01 - Minutes 0..59 Unsigned integer

    66F7h 1 Ore evento nr. 01 Event nr. 01 - Hours 0..23 Unsigned integer

    66F8h 1 Giorno evento nr. 01 Event nr. 01 - Day 0..31 Unsigned integer

    66F9h 1 Mese evento nr. 01 Event nr. 01- Month 1..12 Unsigned integer

    66FAh 1 Anno evento nr. 01 Event nr. 01 - Year 0..99 Unsigned integer

    Il significato del codice dellevento puo essere determinato nella seguente tabella. In caso non siano registrati eventi viene ritornato il codice 0.The meaning of the event code can be found in the following table. In case there is no recorded event code 0 will be returned.

    Num Cod. Messaggio0 E01 Modalit selezionata RESET

    1 E02 Modalit selezionata MAN

    2 E03 Modalit selezionata AUT3 E04 Modalit selezionata TEST

    4 E05 Motore in moto (alt. c.b.)

    5 E06 Motore in moto (frequenza generatore)

    6 E07 Motore in moto (tensione generatore)

    7 E08 Motore in moto (segnale 'W')

    8 E09 Arresto motore

    9 E10 Tentativo di avviamento

    10 E11 Comando di START manuale

    11 E12 Comando di STOP manuale

    12 E13 Comando manuale contattore di rete

    13 E14 Comando manuale contattore generatore

    14 E15 Tensione rete nei limiti

    15 E16 Tensione rete fuori dai limiti

    16 E17 Contattore rete chiuso

    17 E18 Contattore rete aperto18 E19 Tensione generatore nei limiti

    19 E20 Tensione generatore fuori dai limiti

    20 E21 Contattore generatore chiuso

    21 E22 Contattore generatore aperto

    22 E23 Inizio del controllo remoto

    23 E24 Fine del controllo remoto

    24 E25 Accesso al menu Utility dalla tastiera frontale

    25 E26 Accesso al menu Generale dalla tastiera frontale

    26 E27 Accesso al menu Batteria dalla tastiera frontale

    27 E28 Accesso al menu Avviamento motore dalla tastiera frontale

    28 E29 Accesso al menu Controllo motore dalla tastiera frontale

    29 E30 Accesso al menu Controllo rete dalla tastiera frontale

    30 E31 Accesso al menu Controllo generatore dalla tastiera frontale

    31 E32 Accesso al menu Protezione generatore dalla tastiera frontale

    32 E33 Accesso al menu Test e manutenzione dalla tastiera frontale

    33 E34 Accesso al menu Porta di comunicazione dalla tastiera frontale

    34 E35 Accesso al menu Varie dalla tastiera frontale

    35 E36 Accesso al menu Input programmabili dalla tastiera frontale

    Cod. MessageE01 RESET mode select

    E02 MAN mode select

    E03 AUT mode selectE04 TEST mode select

    E05 Motor running (alt. c.b.)

    E06 Motor running (generator frequency)

    E07 Motor running (generator voltage)

    E08 Motor running (signal 'W')

    E09 Motor stop

    E10 Starting attempt number

    E11 START manual command

    E12 STOP manual command

    E13 Mains contactor manual command

    E14 Generator contactor manual command

    E15 Mains voltage into limits

    E16 Main voltage out of limits

    E17 Mains contactor close

    E18 Mains contactor openE19 Generator voltage into limits

    E20 Generator voltage out of limits

    E21 Generator contactor close

    E22 Generator contactor open

    E23 Start remote control

    E24 End remote control

    E25 Access to utility menu from front keyboard

    E26 Access to general menu from front keyboard

    E27 Access to battery menu from front keyboard

    E28 Access to starting motor menu from front keyboard

    E29 Access to engine control menu from front keyboard

    E30 Access to mains control menu from front keyboard

    E31 Access to engine control menu from front keyboard

    E32 Access to engine protection menu from front keyboard

    E33 Access to test & maintenance menu from front keyboard

    E34 Access to communication port menu from front keyboard

    E35 Access to miscellaneous menu from front keyboard

    E36 Access to programmable input menu from front keyboard

  • 8/13/2019 Rgk60 Modul Lovato 3 Modbus Protokol

    19/19

    Cod. MessageE37 Access to programmable output menu from front keyboard

    E38 Access to optional programm. out menu from front keyboard

    E39 Access to optional programm. Input menu from front keyboard

    E40 Access to alarms table 1 menu from front keyboard

    E41 Access to alarms table 2 menu from front keyboard

    E42

    E43 Access to utility menu from remote control

    E44 Access to general menu from remote control

    E45 Access to battery menu from remote control

    E46 Access to starting motor menu from remote controlE47 Access to engine control menu from remote control

    E48 Access to mains control menu from remote control

    E49 Access to engine control menu from remote control

    E50 Access to engine protection menu from remote control

    E51 Access to test & maintenance menu from remote control

    E52 Access to communication port menu from remote control

    E53 Access to miscellaneous menu from remote control

    E54 Access to programmable input menu from remote control

    E55 Access to programmable output menu from remote control

    E56 Access to optional programm. out menu from remote control

    E57 Access to optional programm. Input menu from remote control

    E58 Access to alarms table 1 menu from remote control

    E59 Access to alarms table 2 menu from remote control

    E60

    E61 Software resetE62 Power down

    E63 Parameters to default

    Num Cod. Messaggio36 E37 Accesso al menu Output programmabili dalla tastiera frontale

    37 E38 Accesso al menu Input optional dalla tastiera frontale

    38 E39 Accesso al menu Output optional dalla tastiera frontale

    39 E40 Accesso al menu Tabella Allarmi 1 dalla tastiera frontale

    40 E41 Accesso al menu Tabella Allarmi 2 dalla tastiera frontale

    41 E42

    42 E43 Accesso al menu Utility da controllo remoto

    43 E44 Accesso al menu Generale da controllo remoto

    44 E45 Accesso al menu Batteria da controllo remoto

    45 E46 Accesso al menu Avviamento motore da controllo remoto46 E47 Accesso al menu Controllo motore da controllo remoto

    47 E48 Accesso al menu Controllo rete da controllo remoto

    48 E49 Accesso al menu Controllo generatore da controllo remoto

    49 E50 Accesso al menu Protezione generatore da controllo remoto

    50 E51 Accesso al menu Test e manutenzione da controllo remoto

    51 E52 Accesso al menu Porta di comunicazione da controllo remoto

    52 E53 Accesso al menu Varie da controllo remoto

    53 E54 Accesso al menu Input programmabili da controllo remoto

    54 E55 Accesso al menu Output programmabili da controllo remoto

    55 E56 Accesso al menu Input optional da controllo remoto

    56 E57 Accesso al menu Output optional da controllo remoto

    57 E58 Accesso al menu Tabella Allarmi 1 da controllo remoto

    58 E59 Accesso al menu Tabella Allarmi 2 da controllo remoto

    59 E60

    60 E61 Reset software61 E62 Mancanza alimentazione

    62 E63 Parametri a default